CFL Series – SG

Cable Fault Locator

SCOPE offers CFL Series, Cable Fault Locator Test System, the ultimate solution for locating all types of underground cable faults in minimum time, thus saving long outages and consequential revenue loss & inconvenience. SCOPE offers a full range of products required for fault location of LT/HT power and telecom cables. It includes various models of Surge Generators (Thumpers), Pre-Loca-tors, Pin-Pointers, SIM Filters and Audio Generators. The utility of Surge Generators can be further enhanced by optional in-built features like DC Hi-pot, Burn Down and Sheath Fault Locator. Appropriate models can be chosen and product configuration can be optimized based on application. Various constituent models of Cable Fault Locator Test System are: Surge Generator (Thumper): CFL SG 1605 / 1610 / 1620 / 3210 / 3215 / 3220 Pre Locator: CFL PL2 / PL2+ / PL3 / PL3+ / PL4+ Pin Pointer cum Route Tracer: CFL PP3 / PP3+ Audio Generator: CFL AG2 SIM Filter: CFL SIMF Cable Identification System: CFL CIS Soft Discahrge Rod: CFL DDR series Cable Fault Surge Generator: CFL SG Series CFL SG Series offer voltages up to 16kV / 32kV and energy up to 2000J.
  • Compact, rugged design
  • Key-lock Switch to restrict unauthorized operation
  • Variac Zero, HV Switch & Output Plug Interlock for HV circuit
  • Over-heat Protection at 70°C
  • DC Test System (Hi-Pot, Burn Down & Sheath Fault)
  • Over-current Trip – in DC Test System
  • Earth Indication Emergency Off

TECHNICAL DATA

Full Product Specifications

Parameters CFL SG 1605 / SG 1610 / SG 1620 CFL SG 3210 / SG 3215 / SG 3220
Output Voltage Range 0-4, 0-8, 0-16kV 0-8, 0-16, 0-32kV
Output Energy 500J / 1000J / 2000J 1000J / 1500J / 2000J
Impulse Period Sequence Single Impulse / 3S / 6S / 9S or other as desired
Fault Distance Measurement

Modes Supported

ICM (Impulse Current Method), SIM (Secondary Impulse Method)
Output Indication Moving Coil Meters
Power 230V AC ±10%, 50/60Hz
Housing Elegant, rugged aluminium housing Or mounted on optional trolley
Dimensions 532 X 422 X 654 mm 700 X 700 X 900 mm
Weight (approx.) 55 kg / 60 kg / 65 kg 95 kg / 105 kg / 115 kg
Optional ‘DC Hi-Pot’ Mode
DC Hi-Pot Ranges Voltage: 0–32kV, Current: up to 24mA
Optional ‘Burn Down’ Mode
DC Burn Down Ranges Voltage: 0-8, 0-16, 0-32kV, Current: 0-240, 0-120, 0-60mA
Optional ‘Sheath Fault Locator’ Mode
DC Sheath Fault Ranges Voltage: 0-8kV, Current: 0-240mA

Test Timing Intervals: Single Impulse, 3S / 6S / 9S or other as desired

Related Products

AR700

The AR700 measures acoustic signals with multiple relocatable acoustic sensors mounted on the transformer. The software determines the defect location

PD Analyser

This is an ‘All in One’ solution for detection, analysis & localisation of partial discharges in the insulation of high-voltage

BLUe Series